EA990 series UPS use double conversation technology with a very advanced design criteria improves the performance of components, minimizes the quantity of raw material used on the magnetic and reduces the number of semiconductors thus reducing servicing time and ownership costs. This UPS has high efficiency (>93%) and input power factor (>0.99) built-in output isolation transformer. The inverter transformer prevents the direct feed-through of the battery potential into the critical load and allows a very high rejection ratio of the power supply disturbances (spikes, surges etc).
Features
Online double-conversion with DSP control
IGBT rectifier and high input power factor(>0.99)
High efficiency 93%
Low input distortion: THD<5%
Generator compatible
Output isolation transformer
Inverter IGBT technology with high frequency communication
High immunity to external disturbances
Independent control on the three inverter phases
High instantaneous overload capacity
Capability of supplying distorted loads, containing output voltage distortion with crest factors
Front access makes maintenance and replacement easily, save space
Intelligent self diagnose function, all kinds of fault protection, large capability of history record storage
High MTBF(>200, 000h)
Low MTTR(<0.5h)
Standard emergency power off (EPO)
Standard RS232/RS485/Dry contact communication port
Optional SNMP communication port
Optional N+1 redundancy parallel up to 3 units
MODEL |
EA99160 |
EA99200 |
EA99250 |
EA99300 |
EA99400 |
EA99500 |
Capacity |
160KVA
128KW |
200KVA
160KW |
250KVA
200KW |
300KVA
240KW |
400KVA
320KW |
500KVA
400KW |
INPUT |
|
Rated Voltage |
380V/400V/415VAC |
Voltage Range |
±15%,starting range
±20%,working range |
Rated Frequency |
50/60Hz |
Frequency Range |
50/60Hz ±5Hz |
Power Factor |
≥0.99 |
Total Harmonic Distortion (THDi) |
≤5% |
Bypass Voltage Range |
±20% |
ECO Voltage Range |
±10% |
OUTPUT |
|
Voltage |
380V/400V/415VAC |
Voltage Regulation |
±1% |
Frequency |
Synchronized with utility on AC mode;50/60Hz±0.1% on battery mode |
Waveform |
Pure sine wave |
Crest Factor |
3:1 |
Total Harmonic Distortion(THDV) |
≤1%(Linear load);≤5%(Non-linear load) |
Transfer Time |
AC mode to battery mode :0ms
Inverter model to bypass mode:0ms
Inverter model to ECO mode:5-10ms |
Inverter Overload Capability |
105%-110%:Transfer to bypass after 60mins;
111%-125%:Transfer to bypass after 10mins;
125%-150%:Transfer to bypass after 1mins;
150%-200%:Transfer to bypass after 200 ms;
>200%: power off after 100 ms |
Bypass Overload Capability |
≤150%: Long time running
150%<load<200%: Power off after 1 min
>200%:Power off after 100 ms |
BATTERY |
|
DC Voltage |
600V(12V*50pcs) |
Charger Current |
16A |
20A |
25A |
30A |
40A |
50A |
SYSTEM |
|
Efficiency |
Working mode ≥93%,ECO mode ≥98% |
Alarm |
Battery mode, Battery voltage low, Fans fault etc |
Surge Protection |
IEC60664-1 |
Insulation Resistance |
>2MΩ(500VDC) |
Dielectric Strength |
2820Vdc,No arc in 1min |
IP Class |
IP20 |
EMI |
EN62040-2 |
EMS |
IEC61000-4-2(ESD) |
IEC61000-4-3(RS) |
IEC61000-4-4(EFT) |
IEC61000-4-5(Surge) |
ENVIRONMENT |
|
Humidity |
0~95% RH @ 0~40°C(non-condensing) |
Noise Level |
65dB |
70dB |
75dB |
MANAGEMENT |
|
Communication |
RS232,RS485,Dry contact |
Supports Windows 98/2000/2003/XP/Vista/2008/7/8 |
Optional SNMP |
Power management from SNMP manager and web browser |
PHYSICAL |
|
Dimension(mm) W*D*H |
1210*860*1950 |
2380*860*1950 |
Packing Dimension(mm) W*D*H |
1300*950*2200 |
1300*950*2200(×2) |
Net/Gross Weight(kg) |
1135/1190 |
1355/1410 |
1790/1900 |
2090/2200 |